Tablas presión-temperatura de refrigerantes
Explora las tablas de saturación de 59 refrigerantes con presión, temperatura, punto crítico, GWP, clasificación ASHRAE 34 y rango de aplicación. Cada ficha enlaza a su tabla PT completa y a la calculadora de sobrecalentamiento y subenfriamiento.
- 59 refrigerantes: HFC, HFO, HCFC, CFC, PFC, naturales e hidrocarburos.
- Presión de saturación en kPa absolutos, psig y bar gauge.
- Bubble point, dew point y glide en mezclas zeotrópicas.
- Datos CC BY 4.0 de ProcessConvert y CoolProp, con atribución.
| Refrigerante | Familia | Seguridad | GWP | T crítica | Rango |
|---|---|---|---|---|---|
| R-11R11 | CFC | A1 | 4,750 | 198.0 °C | -110.5 a 198.0 °C |
| R-12R12 | CFC | A1 | 10,900 | 112.0 °C | -157.1 a 112.0 °C |
| R-13R13 | CFC | A1 | 14,400 | 29.9 °C | -175.0 a 29.9 °C |
| R-13I1R13I1 | HFC | A1 | 0 | 123.3 °C | -153.2 a 123.3 °C |
| R-14R14 | PFC | A1 | 7,390 | -45.8 °C | -153.2 a -45.8 °C |
| R-21R21 | HCFC | B1 | 151 | 179.6 °C | -73.2 a 179.6 °C |
| R-22chlorodifluoromethane | HCFC | A1 | 1,810 | 96.2 °C | -157.4 a 96.2 °C |
| R-23R23 | HFC | A1 | 14,800 | 26.1 °C | -155.1 a 26.1 °C |
| R-32difluoromethane | HFC | A2L | 675 | 78.1 °C | -136.8 a 78.1 °C |
| R-40R40 | HCFC | A1 | 13 | 145.5 °C | -43.2 a 145.5 °C |
| R-41R41 | HFC | A1 | 92 | 44.1 °C | -143.3 a 44.1 °C |
| R-50Methane | hidrocarburo | A3 | 28 | -82.6 °C | -182.5 a -82.6 °C |
| R-113R113 | CFC | A1 | 6,130 | 214.1 °C | -36.2 a 214.1 °C |
| R-114R114 | CFC | A1 | 10,040 | 147.5 °C | 0.0 a 147.5 °C |
| R-115R115 | CFC | A1 | 7,370 | 80.0 °C | -99.6 a 80.0 °C |
| R-116R116 | PFC | A1 | 12,200 | 19.9 °C | -100.1 a 19.9 °C |
| R-123R123 | HCFC | B1 | 77 | 183.7 °C | -107.2 a 183.7 °C |
| R-124R124 | HCFC | A1 | 609 | 122.3 °C | -153.2 a 122.3 °C |
| R-125R125 | HFC | A1 | 3,500 | 66.0 °C | -100.6 a 66.0 °C |
| R-134a1,1,1,2-tetrafluoroethane | HFC | A1 | 1,430 | 101.1 °C | -103.3 a 101.1 °C |
| R-141bR141b | HCFC | A1 | 725 | 204.4 °C | -103.5 a 204.4 °C |
| R-142bR142b | HCFC | A2 | 2,310 | 137.1 °C | -130.4 a 137.1 °C |
| R-143aR143a | HFC | A2 | 4,470 | 72.7 °C | -111.8 a 72.7 °C |
| R-152AR152A | HFC | A2 | 0 | 113.3 °C | -118.6 a 113.3 °C |
| R-161R161 | HFC | A1 | 12 | 102.1 °C | -143.2 a 102.1 °C |
| R-170Ethane | hidrocarburo | A3 | 6 | 32.2 °C | -182.8 a 32.2 °C |
| R-218R218 | PFC | A1 | 8,830 | 71.9 °C | -147.7 a 71.9 °C |
| R-227EAR227EA | HFC | A1 | 0 | 101.8 °C | -126.8 a 101.8 °C |
| R-236EAR236EA | HFC | A1 | 0 | 139.3 °C | -30.2 a 139.3 °C |
| R-236FAR236FA | HFC | A1 | 0 | 124.9 °C | -93.6 a 124.9 °C |
| R-245caR245ca | HFC | A1 | 693 | 174.4 °C | -77.2 a 174.4 °C |
| R-245faR245fa | HFC | B1 | 1,030 | 153.9 °C | -102.1 a 153.9 °C |
| R-290Propane | hidrocarburo | A3 | 3 | 96.7 °C | -187.6 a 96.7 °C |
| R-365MFCR365MFC | HFC | A1 | 0 | 186.9 °C | -34.2 a 186.9 °C |
| R-404AR-125/R-143a/R-134a (44/52/4 wt%) | mezcla zeotrópica | A1 | 3,922 | 72.1 °C | -73.2 a 72.1 °C |
| R-407CR-32/R-125/R-134a (23/25/52 wt%) | mezcla zeotrópica | A1 | 1,774 | 86.2 °C | -73.2 a 86.2 °C |
| R-410AR-32/R-125 (50/50 wt%) | mezcla zeotrópica | A1 | 2,088 | 71.3 °C | -73.2 a 71.3 °C |
| R-507AR-125/R-143a (50/50 wt%) | mezcla zeotrópica | A1 | 3,985 | 70.6 °C | -73.2 a 70.6 °C |
| R-600n-Butane | hidrocarburo | A3 | 4 | 152.0 °C | -138.3 a 152.0 °C |
| R-600aisobutane (2-methylpropane) | hidrocarburo | A3 | 1 | 134.7 °C | -159.4 a 134.7 °C |
| R-601n-Pentane | hidrocarburo | A1 | 5 | 196.6 °C | -129.7 a 196.6 °C |
| R-601aIsopentane | hidrocarburo | A3 | 5 | 187.2 °C | -160.5 a 187.2 °C |
| R-717anhydrous ammonia | refrigerante natural | B2L | 1 | 132.4 °C | -77.7 a 132.4 °C |
| R-718water | refrigerante natural | A1 | 0 | 374.0 °C | 0.0 a 250.0 °C |
| R-744carbon dioxide | refrigerante natural | A1 | 1 | 31.0 °C | -56.6 a 31.0 °C |
| R-1123R1123 | HFO | A1 | 1 | 58.6 °C | -78.0 a 58.6 °C |
| R-1130(E)R1130(E) | HFO | A1 | 0 | 242.5 °C | -49.8 a 242.5 °C |
| R-1132(E)R1132(E) | HFO | A1 | 0 | 75.7 °C | -33.2 a 75.7 °C |
| R-1150Ethylene | hidrocarburo | A3 | 4 | 9.2 °C | -169.2 a 9.2 °C |
| R-1224YDZR1224YDZ | HFO | A1 | 0 | 155.5 °C | -115.4 a 155.5 °C |
| R-1233zd(E)R1233zd(E) | HFO | A1 | 1 | 165.7 °C | -107.4 a 165.7 °C |
| R-1234yfR1234yf | HFO | A2L | 4 | 94.7 °C | -151.6 a 94.7 °C |
| R-1234ze(E)R1234ze(E) | HFO | A1 | 6 | 109.4 °C | -104.5 a 109.4 °C |
| R-1234ze(Z)R1234ze(Z) | HFO | A1 | 2 | 150.1 °C | -0.2 a 150.1 °C |
| R-1243zfR1243zf | HFO | A1 | 1 | 103.8 °C | -150.8 a 103.8 °C |
| R-1270Propylene | hidrocarburo | A3 | 2 | 91.1 °C | -185.2 a 91.1 °C |
| R-1336mzz(E)R1336mzz(E) | HFO | A1 | 18 | 130.4 °C | -73.0 a 130.4 °C |
| R-1336mzz(Z)R1336mzz(Z) | HFO | A1 | 9 | 171.4 °C | -90.5 a 171.4 °C |
| R-C318RC318 | PFC | A1 | 10,300 | 115.2 °C | -39.8 a 115.2 °C |
Cómo usar las tablas presión-temperatura
La tabla PT relaciona la presión de saturación con la temperatura de cambio de fase. En campo se mide la presión con el manifold y se usa la tabla para estimar la temperatura de evaporación o condensación del refrigerante.
- Identifica el refrigerante y su tabla.
- Mide la presión manométrica y conviértela a absoluta.
- Busca la presión en la tabla y lee la temperatura de saturación.
- Ajusta la presión atmosférica si trabajas en altura.
Presión absoluta, manométrica y vacío
Las tablas se calculan con presión absoluta. La presión manométrica (psig, bar gauge o kPa gauge) se convierte sumando la presión atmosférica local. En vacío, la presión absoluta es menor que la atmósfera y se expresa en µmHg, mTorr o Pa.
- P absoluta = P manométrica + P atmosférica.
- 1 bar = 100 kPa; 1 psi = 6,894757 kPa.
- 760 000 µmHg = 1 atmósfera.
Mezclas zeotrópicas y glide
En mezclas como R-404A, R-407C, R-410A o R-507A la temperatura de cambio de fase no es única. El bubble point marca la aparición de la primera burbuja y el dew point la última gota de líquido; la diferencia es el glide.
- Usa bubble point para la línea de líquido.
- Usa dew point para la línea de succión.
- Reporta el glide al comparar lecturas.
Preguntas frecuentes
¿Qué es una tabla presión-temperatura (PT)?
Es una tabla que relaciona la presión de saturación de un refrigerante con su temperatura de cambio de fase. Permite estimar la temperatura de evaporación o condensación a partir de la presión medida con un manifold.
¿Cómo paso de psig a presión absoluta?
Suma la presión atmosférica local a la presión manométrica. A nivel del mar la atmósfera estándar es 101,325 kPa (14,696 psia); en altura debes usar la presión atmosférica corregida por la altitud.
¿Qué diferencia hay entre bubble point y dew point?
El bubble point es la temperatura a la que aparece la primera burbuja de vapor en una mezcla zeotrópica. El dew point es la temperatura a la que desaparece la última gota de líquido. Su diferencia es el glide.
¿Los datos sirven para diseño definitivo?
Son datos de referencia para diagnóstico y estimación. Para diseño definitivo, verifica con la ficha del fabricante, instrumentos calibrados y la norma aplicable a la instalación.